Installation Drawings
137
Figure 145 Wiring specifications, Liebert FS and Liebert Series 300
Wire
No.
Terminal Designation
Signal
Name
Maximum
Voltage
Maximum
Current
Color
Wire Size
& Type
Maximum
Length
Remarks
From
To
Series 300 UPS - Cable Group # 27 (Flywheel CB IFM) From I1 In UPS Module to TB1 on Liebert FS Module
901
I1-TB1-1
TB1-1
Trip Signal (+)
+24 VDC
100mA
1/C #16
(2.5 mm
2
)
Stranded
500 ft
(150 m)
902
I1-TB1-2
TB1-2
Trip Signal (-)
-24 VDC
100mA
903
I1-TB1-7
TB1-7
Aux Comm
24 VDC
100mA
904
I1-TB1-8
TB1-8
Aux N.O.
24 VDC
100mA
Series 300 UPS - Cable Group # 116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused Disconnect
914
FBO
TB1-1
Line
120VAC
3.5A
1/C #16
(2.5 mm
2
)
Stranded
500 Ft
(150
Meters)
UPS-
Protected
Auxiliary
Control
Power
915
FBO
TB1-2 Neutral
120VAC
3.5A
916 FBO
TB1-3
GND
120VAC 3.5A
1. Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.
2. Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
3. All external wires furnished by others.
4. N.O. = Normally Open; N.C. = Normally Closed; Comm = Common; F.B.O. = Furnished By Others, GND = Ground
5. All wiring must be in accordance with national and local electrical codes.
2. Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
3. All external wires furnished by others.
4. N.O. = Normally Open; N.C. = Normally Closed; Comm = Common; F.B.O. = Furnished By Others, GND = Ground
5. All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_S300_Liebert-FS Rev. 01