Specifications
148
A
PPENDIX
 E.0 S
PECIFICATIONS
Table 36
Technical specifications
INPUT, DC
Float Voltage
350 through 600 VDC; > 520 VDC required for 190kW
Charging Current
5 through 50 Amps per Liebert FS
Rated Input Charging
350-600 VDC; > 520 VDC required for 190kW
Maximum Idling Consumption
Less than 300 W
INPUT, AC
Control Circuit Rating
100-240VAC, 440W, 50/60Hz
OUTPUT, DC
Nominal Power
190 kW
Nominal Delivered Energy
190 kW for 10 seconds
Maximum Delivered Energy
220 kW for 5 seconds
Discharge Voltage (adjustable)
350 through 600 VDC
Rated Output Discharge
350-600 VDC, 250A; > 510 VDC required for 190 kW
DC Voltage Regulation
± 1% steady state
DC ripple
< 2%
Current Short Time
400A
Short Circuit Withstand Current Capacity
(Circuit-breaker/fused terminal block)
20 kADC / 10 kADC
INPUT, AC (AUX)
Auxiliary Voltage
110VAC – 230VAC (50/60Hz)
Auxiliary Power Rating
400VA
ENVIRONMENTAL
Operating Temperature
-20°C to 50°C (-4°F to 122°F)
Startup Temperature
0°C to 50°C (32°F to 122 °F)
Non-Operating Temperature
-20°C to 80°C (-4°F to 176 °F)
Humidity
5% to 95% non-condensing
Operating Altitude
Up to 3,000 meters (9,842 feet) above sea level
Non-Operating Altitude
Up to 12,000 meters (39,370 feet) above sea level
Operating Audible Noise Level
<50 dBa at 1 meter in Ready mode; less than 65 dBa 
when discharging
Heat Dissipation
Less than 300W (1,025 BTU/h)
Cabinet Environmental Rating
NEMA 1 / IP 30
Pollution Degree
3 (Industrial)
PHYSICAL DATA
Dimensions (W x D x H)
63 x 83 x 181 cm (25 x 33 x 71 in)
Footprint
0.5 m² (5.7 sq ft)
Weight
590 kg (1,300 lb)
Shipping Package Weight
660 kg (1,460 lb)
Cable Access
Top or Side Entry
STANDARDS / MARKINGS
UL Listed
cUL Listed
CE Mark
1.  For discharge voltages below 510 VDC, contact Liebert (1-800-LIEBERT) or your local representative.