Emerson Series 600 User Manual

Page of 168
General System Information
6
Figure 4
One or more Liebert FS units in parallel with one or more battery strings, battery cabinets or 
batteries in racks
1.2.1 General Specifications
Table 2 summarizes the technical specifications of the Liebert FS.
For more-detailed technical specifications, refer to Technical specifications on page 148.
Table 2
General system specifications
Rated Power Delivery
Dependent upon the duration required;
refer to Figure 5
Input Voltage (DC)
360 through 600 VDC; > 520 VDC required for 190kW
Output Voltage (DC)
350 through 590 VDC; > 510 VDC required for 190kW
Input Voltage Aux. (AC)
85 VAC – 265 VAC (47-63Hz)
Operating Temperature
-20°C to 50°C (-4°F to 122°F)
Non-Operating Temperature
-20°C to 80°C (-4°F to 176°F)
Dimensions (W x D x H)
63 x 83 x 180 cm (25 x 33 x 71 in)
Total Weight
590 kg (1,300 lb)
Loads
UPS Block Diagram
UPS
 DC Bus
AC
DC
DC
AC
Liebert
FS Unit  1
Liebert
FS Unit  2
Liebert
FS Unit N
Utility 
Power
Battery 1
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
Battery 2
Battery N