Emerson Series 600 User Manual

Page of 168
Installation
24
4.1.2 Wood Floor Mounting
Determine which of these cases applies to your installation:
• For wood flooring over concrete, follow the instructions in 4.1.1 - Concrete, Masonry or Stone 
• For wood flooring on joists, follow the instructions in this section.
Wood Floor Mounting Parts
• Two (2) cabinet mounting brackets (previously secured Liebert FS cabinet to shipping pallet)
• Four (4) (1/2" diameter x 2-1/2" long) [or 12.7mm diameter x 63.5mm] lag screws (not included in 
mounting kit) are recommended
• One floor mounting template, see Figure 149
• Four (4) 1/2" diameter x 3/4" long (12.7mm diameter x 20mm long) hex bolts (from shipping pack-
Wood Floor Mounting Tools
The following tools are needed for the cabinet wood floor mounting:
• Electric drill
• 1/4" (7mm) drill bit
• Drill bit—used for pilot hole—for example, 1/8" (3.2mm) diameter
• Shop vacuum cleaner (to remove dust from hole when drilling)
• 3/4" (19mm) combination wrench
• 18mm combination wrench
Wood Floor Mounting Instructions 
Installation in wood floor on joists does not require drop-in anchors.
1. Prepare a clean, level surface, free of obstructions, for installation of the mounting kit.
2. Tape the floor mounting template (Figure 149) to the installation location.
3. Drill pilot holes, remove the template and use a 1/4" (7mm) drill bit to drill holes 2.5" (64mm) 
deep.
4. Match mounting brackets with holes under base of cabinet (see Figure 21). Make sure that the 
bracket holes align with the mounting spots on the underside of the cabinet and secure brackets 
with the four hex bolts retained from the shipping package. Each bolt is 1/2" diameter x 3/4" long 
(12.7mm diameter x 20mm long). Tighten the bolts with a torque wrench at 40 foot-pounds 
(54 N-m).
5. Insert two lag screws through bracket mounted at rear of cabinet leaving head with 1/2" (12.7mm) 
gap above floor (see Figure 22).
6. Position and align cabinet and bracket slots with the newly drilled holes at rear and position 
cabinet such that bolts fit in bracket slots (see Figure 22).
7. Insert two (2) lag screws through bracket mounted at front of cabinet (see Figure 23).
8. Check the bubble level on the floor of the cabinet on the right hand side of the Power Conversion 
Module (see Figure 24). The Liebert FS is sufficiently level when the bubble is within the outer of 
the two circles. If the bubble is outside the outer circle, use the leveling feet to adjust until bubble 
is within the outer circle.
9. Once the cabinet is level, firmly tighten the front lag screws to a torque 40 foot-pounds (54 N-m).
!
CAUTION
Ensure that holes are centered in the joist.