Emerson Remote Monitoring Panel User Manual

Page of 28
Operation
20
3.8
Prompt (Popup) Windows
The prompt window is displayed during the operation of the system to alert the user to certain condi-
tions and / or to require user confirmation of a command.
3.9
Dynamic Energy Flow Chart and UPS Help Screen
This screen displays a mimic diagram of the UPS that includes energy flow and status of isolation and 
transfer switches. Press the “Help” key to activate this screen. Press “Help” again to toggle between 
this screen and the main screen.
NOTE
The items in Table 14 are visible form the RMP, but the controls for them are available only at 
the UPS.
Table 14
Prompt windows, meanings controlled at UPS only
Prompt
Meaning
Transfer with interrupt, please confirm or cancel
Inverter and Bypass supplies are not synchronized and 
any load transfer between the supplies will cause a brief 
load interruption. 
The load is too high to be transferred with interrupt
The total load must be less than the capacity of one unit 
to allow a parallel system to perform an interrupted 
transfer from bypass to inverter. 
This Operation Leads to Output Shutdown, Confirm or 
Cancel
No alternative supply is available and any Inverter Off 
operation will cause the load to be de-energized.
This operation leads to inverter overload, confirm or 
cancel
The turn-off this inverter will lead to the overload of 
remaining inverter(s) in a parallel system.
Turn on more UPS to carry current load 
The number of paralleled inverters already turned on is 
insufficient to carry the existing load.
Battery will be depleted, confirm 
Battery Capacity test discharges the battery 100%
System self test finished - everything is ok. 
No action required
System self test finished - Please check the current 
warnings.
Check “Current Records” window
Enter control password
Required for Battery or UPS test (default = 12345)
Battery Self Test aborted, condition not met
Battery self-test condition is not enough. User should 
check whether battery state is boost charging and 
whether load level is greater than 20 percent.
Battery Refresh Charge aborted, condition not met
Boost charging condition is not enough, such as (No 
battery, charger has failed, etc.).
Table 15
Prompt windows, meanings controlled at RMP
Prompt
Meaning
Communication with UPS failed
 
The communication between RMP and UPS failed.
 
Loading data from UPS
The RMP are loading data from UPS
 
Remote Monitoring Panel silence
The RMP unit has been muted.
 
Remote Monitoring Panel silence off
The RMP silence is off
 
Remote Monitoring Panel firmware updating
The RMP are updating firmware from ParameSet tool.
 
Firmware is not compatible with UPS
T
he RMP firmware is not compatible with UPS