Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
59
Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
7.5
Electrical Characteristics
7.5.1
Termination Type, Recommended Wire Size, Recommended Lugs
AC Input
1
Wire sizes based on recommendations of the American National 
Standards Institute (ANSI) approved National Fire Protection 
Association's (NFPA) National Electrical Code (NEC). Table 310-16 
for copper wire at 90°C conductor temperature operating in ambient 
of 35°C was used. For other operating ambient temperatures, refer 
to the NEC. For operation in countries where the NEC is not 
recognized, follow applicable codes.
Equipment grounding conductors must be provided with the AC 
input conductors supplied to the module. Frame ground terminals 
must be connected to earth ground, not power system neutral. 
Equipment grounding conductor size based on recommendations of 
the NEC Table 250-122 for copper wire. When aluminum or copper 
clad aluminum grounding conductor is used, refer to Table 250 122 
for increased conductor size. For operation in countries where the 
NEC is not recognized, follow applicable codes.
Cabinet Frame Grounding
Table 10
AC Input and AC Input Grounding (per DC UPS module)
AC Input
Input 
Voltage
Maximum
Input
Current
Terminal
Type
Recm.
Wire 
Size
1
Conduit Size
480Vac
92A
Screw
Clamp
2/0 AWG
2"
400Vac
110A
380Vac
116A
AC Input Grounding
Input 
Voltage
Bolt
Size
Recm.
Wire
Size
1
Conduit 
Size
Recommended Lug
(Thomas & Betts P/N)
Compression
1-Hole; 3/8" Bolt
480Vac
5/16" (M8)
1/0 AWG
2"
54109
400Vac
Table 11
Cabinet Frame Grounding (per DC UPS module)
Bolt
Size
Recm.
Wire
Size
Recommended Lug
(Thomas & Betts P/N)
Compression
1-Hole; 3/8" Bolt
3/8" (M10)
6 AWG
54136