Emerson LXP48F1 User Manual

Page of 43
System Application Guide 
SAG582135000 
Spec. No. 582135000 (Model LXP48F1) 
Issue AE, January 31, 2007 
Page 25 of 43 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
5
  Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature. 
6
  Load lugs are one-hole for 1/4" bolt clearance.  Load Return lugs are two-hole for 1/4" bolt  
clearance on 5/8" centers.  Refer to drawing 031110100 for lug crimping information. 
 
 
Distribution (Load) Wire Sizes and Lugs—List GA 
Features 
♦  In each List GA Distribution Cabinet, Screw compression terminals are provided for connecting Load and 
Load Return wiring.  Maximum size of wire to be connected to a single position is 14 AWG.   
 
 
Battery Wire Sizes and Lugs—All Lists 
Features 
♦  List BD, BL, BS, LB, LD, LS, LX:  In each Distribution Cabinet, lug-terminated battery conductors are 
connected to the battery terminals.  Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of 
customer provided two-hole lugs.     
 
List GA:  In each Distribution Cabinet, lug-terminated battery conductors are connected to the battery 
terminals.  Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of customer provided two-hole 
lugs. 
♦  For lug mounting hole size and spacing dimensions, refer to the illustration provided in the 
Restrictions 
All lugs for customer connections must be ordered separately. 
Customer must supply lug-mounting hardware. 
Ordering Notes 
1)  Battery wire size varies depending on load, therefore no specific information is provided for wire size.  
 for recommended wire sizes and lugs at rated maximum Distribution Cabinet load.  
When making connections, observe correct polarity. 
2)  For other available lugs and hardware, refer to drawings 031110100 through 031110300.