User Instructions 
Issue AB, March 22, 2012 
Spec. No. 581127000 (Model 710
NPBA
 
Page 16 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Procedure 
1)  With the Main screen displayed, press ENT to go to the Main Menu.  Navigate to 
and select 
Settings” (ENT). 
2)  If a password screen opens, a password must be entered to allow the User to 
make adjustments.  If a password was previously entered and has not yet timed 
out, skip this step and proceed to step 3).  Otherwise, to enter a password, with 
the cursor at the User Name field 
(default is “Admin”), press the down arrow key 
to move cursor down to the password line.  Press ENT
.  “0” is highlighted.  Press 
the up arrow key once to change the “0” to”1” (default password is “1”), then 
press ENT twice.  (Note:  If you have been assigned a unique User Name and 
password, follow this procedure to enter these.)
 
3)  With the Settings menu screen displayed, navigate to and select 
Rectifier” 
(ENT) / 
All Rect Set” (ENT). 
4)  Navigate to 
Current Limit Pt”.  The current limit in amperes is displayed.  If no 
change is required, go to step 6).  To make a change, proceed with step 5). 
5) 
With the cursor at “Current Limit Pt”, press ENT to change the current limit point.  
Use the up or down arrow keys to set as desired, then press ENT
6)  Return to the Main screen by repeatedly pressing ESC (escape). 
Clearing a Rectifier Communications Fail Alarm after Removing a Rectifier 
If a rectifier module is removed from the system, a rectifier communications failure alarm 
is generated.  If the rectifier module will not be replaced, the alarm should be cleared as 
described in the following procedure. 
Procedure 
1)  With the Main screen displayed, press ENT to go to the Main Menu.  Navigate to 
and select 
Manual” (ENT). 
2)  If a password screen opens, a password must be entered to allow the User to 
make adjustments.  If a password was previously entered and has not yet timed 
out, skip this step and proceed to step 3).  Otherwise, to enter a password, with 
the cursor at the User Name field 
(default is “Admin”), press the down arrow key 
to move cursor down to the password line.  Press ENT
.  “0” is highlighted.  Press 
the up arrow key once to change the “0” to”1” (default password is “1”), then 
press ENT twice.  (Note:  If you have been assigned a unique User Name and 
password, follow this procedure to enter these.)
 
3)  With the Manual menu screen displayed, navigate to and select 
Rectifier” (ENT) 
All Rect Ctrl” (ENT). 
4)  Navigate to 
Clear Comm Fail”.  Press ENT.  “Yes” highlights. 
5)  Press ENT to select the operation.  Press ENT again to confirm. 
6)  Return to the Main screen by repeatedly pressing ESC (escape). 
Clearing a Converter Communications Fail Alarm after Removing a Converter 
If a converter module is removed from the system, a converter communications failure 
alarm is generated.  If the converter module will not be replaced, the alarm should be 
cleared as described in the following procedure. 
Procedure 
1)  With the Main screen displayed, press ENT to go to the Main Menu.  Navigate to 
and select 
Manual” (ENT).