Emerson 710NPBA User Manual

Page of 60
UM581127000 
User Instructions 
Issue AB, March 22, 2012 
Spec. No. 581127000 (Model 710
NPBA
 
Page 36 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
SM-DU+ and Shunt Interface Assembly Replacement 
Procedure 
1)  Performing this procedure may activate external alarms.  Do one of the following.  
If possible, disable these alarms.  If these alarms cannot be easily disabled, 
notify the appropriate personnel to disregard any future alarms associated with 
this system while the procedure is being performed. 
Danger:  Performing the next steps exposes service personnel to battery 
potential.  Exercise extreme caution not to inadvertently contact or 
have any tool inadvertently contact any energized electrical 
termination. 
2)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
Warning:  Damage to the circuit card may result if the next step is not followed. 
3)  Connect an approved grounding strap to your wrist.  Attach the other end to a 
suitable ground. 
4)  Carefully label the wires connected to the shunt input terminal blocks on circuit 
card.  These wires must be connected to the same terminals on the replacement 
circuit card.  Refer to Figure 4-12. 
5)  Carefully label the connectors plugged into the circuit card.  These connectors 
must be plugged into the same connectors on the replacement circuit card.  
Refer to Figure 4-12. 
Danger:  In the next step, external wiring may be energized from an external 
source.  DO NOT allow bare wire ends to contact any grounded or 
energized object. 
6)  Remove the external wiring from the shunt input terminal blocks.  DO NOT allow 
the bare wire end to contact any grounded or energized object.  Isolate the wire 
end with electrical tape.  Repeat for each wire to be removed. 
7)  Unplug all connectors plugged into the circuit card. 
8)  Remove the screw securing the SM-DU+ and Shunt Interface Assembly to the 
bottom of the distribution cabinet, and remove the assembly. 
9)  SM-DU+:  In this step, ensure you do not intermix the old and replacement circuit 
cards.  Set the switches on the replacement circuit card to the same settings as 
the old circuit card.  Switch settings are documented in CHAPTER 3. SETTING 
JUMPERS AND SWITCH OPTIONS of the Power System Installation 
Instructions (IM581127000). 
10) Slide the replacement SM-DU+ and Shunt Interface Assembly into the mounting 
position inside the distribution cabinet, and secure with the screw removed from 
the old assembly. 
11) Plug all connectors removed from the old circuit card into the same position on 
the replacement circuit card. 
Danger:  In the next step, external alarm wiring may be energized from an 
external source.  DO NOT allow bare wire ends to contact any 
grounded or energized object. 
12) Reconnect the external wiring to the correct terminals on the shunt input terminal 
blocks.  First remove the electrical tape that was applied to the bare wire end in a 
previous step.  DO NOT allow the bare wire end to contact any grounded or 
energized object.  After securing the wire, gently tug on the wire to ensure that it