Emerson NX User Manual

Page of 48
Operation
17
Liebert
®
NX
2.4.4 Remote Emergency Power Off
The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS 
system. It usually is installed in the same room as the critical load equipment. This mode can also be 
initiated by an automatic contact closure in the same external circuit as the manually operated 
switch.
When the Remote Emergency Power Off switch is operated, the UPS will shut down and open bypass 
circuit breakers. All power through the UPS is removed from the load. Typically, the REPO circuit 
also opens the circuit breakers that provide power to the bypass lines and the UPS controls. Refer to 
Figure 18 Remote Emergency Power Off
2.5
Manual Operations—All Systems
The Liebert NX UPS is designed to function while unattended by an operator. The system control 
logic automatically handles many important functions, as explained in 2.16 - Automatic Operations. 
Other procedures must be performed manually.
Manual procedures available to the operator include startup, load transfers and shutdowns. These 
procedures are performed by using the touchscreen and some manually operated circuit breakers and 
switches.
This section lists typical step-by-step instructions.
• Startup—Including initial startup, recovering from input power failure, recovering from DC 
source shutdown and recovering from shutdowns for emergencies or maintenance.
• Load Transfers-Including transfers from UPS to bypass and retransfers from bypass to the UPS 
system.
• Maintenance Bypass Load Transfers—Including transfers from internal bypass to maintenance 
bypass and transfers from maintenance bypass to internal bypass.
• Shutdowns—Including module shutdowns for maintenance and emergency shutdowns.
NOTE
The following procedure assumes that the UPS installation inspection and initial startup have 
been performed by Emerson Network Power
®
 Liebert Services. An Emerson-authorized 
representative must perform the initial system startup to ensure proper system operation.
DC 
Bus
BFB
UPS Module
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass 
AC Input
UPS Output
Critical 
Load
DC 
Bus