Emerson 40-200KVA User Guide
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Liebert
®
BDC
™
44
Figure 21 Liebert
®
BDC connection to UPS
NOTES
1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in
their final installed location.
2. All interconnection hardware supplied by Emerson
®
.
3. AC connections must be made to the UPS module before attaching Liebert BDC to UPS module.
4. All cabling will be field-supplied when a Liebert BDC is configured as a stand-alone cabinet.
5. Liebert BDCs must attach to the right side only of the Liebert NX
4. All cabling will be field-supplied when a Liebert BDC is configured as a stand-alone cabinet.
5. Liebert BDCs must attach to the right side only of the Liebert NX
™
.
6. Refer to the individual drawing of each piece of equipment for additional details.
Table 16
Table 16
Control wiring for Liebert
®
NX
™
UPS to Liebert BDC
From
To
Liebert NX UPS
Monitor Board X1-J21
Liebert BDC Terminal Strip (TB2)
J21-3 INV_S
TB1-2
J21-4 INV_C
TB2-1
NX 480 UPS Parallel Board X3
Liebert BDC Terminal Strip (TB2)
X3-1-EXT-MAINT
TB2-3
X3-2-GND2
TB2-4