Emerson 40-200KVA User Guide

Page of 132
Installation Drawings
51
8.0
I
NSTALLATION
 D
RAWINGS
The diagrams in this section illustrate the key mechanical and electrical characteristics of the 
Liebert
®
 NX
 UPS System cabinets.
Figure 25 Outline drawing, Liebert NX 40-120kVA
Table 22
Weights, Liebert NX 40-120kVA
kVA Rating
UPS Weight, lb (kg)
Heat
BTU/Hr
Cooling Air
CFM
Net
Crated
40
1290 (585
1440 (653)
11612
620
60
1290 (585
1440 (653)
15204
620
80
1290 (585
1440 (653)
20273
620
80*
1422 (645
1572 (713)
19700
920
100*
1422 (645
1572 (713)
23496
920
120
1422 (645
1572 (713)
28196
920
Source: U3819203, Rev. 4
1. All dimensions are in inches (mm).
2. Minimum clearance 36" front and 8" top
    required for air exhaust.
3. Keep cabinet within 15 deg. of vertical
    while handling.
4. Top and bottom cable entry available 
    through removable access plates. 
    Remove punch to suit conduit size and replace.
5. Color: Black.
6. Unit bottom is structurally adequate for forklift 
    handling.
7. Open door to replace air filter, washable type.
8. Side panels are removed between adjacent units 
    that are bolted together.
9. Leveling feet are not designed to carry the full weight of the
    cabinet. Finger-tighten leveler against the floor, then tighten
    with a wrench less than two turns for friction fit against floor.
Power Cable Entry
3.7 x 22.8 (94x 580)
U3819203
Rev. 4
TOP VIEW 
FRONT
FRONT
FRONT VIEW
FRONT
SIDE VIEW
BOTTOM VIEW
Display
Power Cable Entry
4.9  x 11.4 (125 x290)
1.55 (39) Leveler
to Outside Frame (See Note 9)
1.6 (41) Leveler to Outside Frame
3.5 (90) Caster
To Outside Frame
5.9 (150)
to Outside
Frame
Power
Cable
Entry
DETAIL A
Detail A
1.5 (38) Cable Panel
To Outside Frame
3.7 (94) Caster
To Outside Frame
Caster
Outer Panel
Outer Panel
20.9
(530)
25.5 (648)
23.6 (600)
78.7
(2000)
33.1
(842)
15.4
(390)
20.3
(515)
38.5 (978)
39 (990)
To Display
40.9
(1040)
1.6 (40)
Center
of Gravity
Center
of Gravity