Emerson 40-200KVA User Guide

Page of 132
Installation Drawings
60
Figure 34 Liebert
®
 NX
 40-120kVA cable connections
NOTES
1. All dimensions are millimeters (in.).
2. Top and bottom cable entry available through 
removable access plates. Remove, punch to 
accommodate conduit size and replace.
3. Control wiring and power wiring must be run in 
separate conduit. Output and input cables must 
be run in separate conduit.
4. Aluminum and copper-clad aluminum cables are 
not recommended.
5. All wiring is to be in accordance with national 
and local electrical codes.
20 (.79")
35
(1.38")
158.1
(6.22")
35
(1.38")
36 (1.42")
Output
GND
DC
Bypass
Main
25.4
(1")
6
(.24")
CB1
CB2
CB3
CB5
DETAIL A
600
(23.6")
2000
(78.7")
FRONT VIEW
(with door removed)