Emerson 225-600KVA User Manual

Page of 40
Installation Drawings
13
Liebert
®
 NX
Figure 9
Terminal details, Liebert Top-Terminal Battery Cabinet
Notes
1. All dimensions are in inches (mm)
2.Top and bottom cable entry available through
   removable access plates.
3. Control wiring and power wiring must be run
   in separate conduit.
4. Aluminum and copper-clad aluminum cables
   are not recommended.
5. All wiring must be in accordance with national
   and local electrical codes.
6.  For cabinets ordered as stand-alone, the negative
    and positive terminal bus does not extend to full width of battery cabinet.
7. 24" minimum clearance above unit is required for air exhaust and service access.
1.75
(45)
.56
(14)
1.75 (45)
1.75 (45)
1.75
(45)
1.75
(45)
.53
(14)
See Bus
Termination Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
Top View
Right Side View
Front View
Ground Bus
(See Detail)
* Doors And Covers Removed for Clarity
Ground Bus Detail
+
-
Bus Termination Detail
DO NOT DOUBLE-STACK LUGS 
CB1-3
CB1-3