10      Chapter 1  System Description 
ACTURA Flex 48330
 
Power System  User Manual 
Table 1-5    Configuration of MFU 
No. 
Component 
Description 
1 SPD 
Norminal Dischage Current(8/20μS) 20kA; Ue=385V 
AC input terminals 
Rating Current 150A 
Rectifier AC input MCB 
Rating Current 25A 
BLVD contactor 
200A or 400A optional 
LLVD contactor 
200A or 400A optional 
6 Shunt 
300A/75mV 
Battery MCB 
100A MCB (up to 5 battery MCBs can be selected to configure) 
Load MCB 
Selected according to user’s requirement 
 
The user can mount the distribution unit into cabinets with widths of 600mm and 
depths of 400mm and 600mm. It has a height of 4.5U (200mm). 
1.5.5    Battery Connection Unit (BCU) 
Outline 
The outline of the Battery Connection Unit (BCU) is illustrated in Figure1-7. 
Enclosure
-48V DC Bus
Battery MCB
 
Figure 1-7    Outline of battery connection unit (BCU) 
Physical size 
Battery Connection Unit (BCU) can be installed in cabinets with widths of 600mm 
and depths of 400mm and 600mm.    BCU has a maximum height of 1.5U (67mm). 
BCU contains 2 to 5 circuit breakers, each with ratings of 100A and 200A. 
Alarm output 
The BCU will generate an alarm if a battery circuit breaker is off. This alarm shall be 
possible to connect to the connector board for display in the Controller.    It shall be 
possible to combine the alarms from 2 BCUs to generate a single alarm in the 
controller.    It shall also be possible to combine the alarm from the BCU with an