54      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
2. Use “
” or “
” to select the submenu “Settings” and press “ENT” to confirm. 
System will then prompt you to input the password.   
 
Enter Password: 
123456 
 
 
 
3. Press "
" or "
" to select the number of password digits. Enter the password 
digit by digit using “
” or “
”. Press “ENT” to confirm and enter the parameter 
setting submenu.   
Settings 
Alarms Settings 
Battery Settings 
AC Settings 
 
 
Parameter Set 
DC Settings 
 Rect Settings 
 Sys Settings 
 
 
Users with different password levels have different authorities. See the following 
table:  
Table 5-9    Password levels and authorities 
Level 
Authority 
Default password 
User Configuration 
of general parameters 
123456 
Operator 
User’s authority, plus resetting system, resetting 
password and modifying system type.   
654321 
Administrator
Operator’s authority, plus modifying password of all 
levels, controling alarm sound volume, browsing system 
parameters that can be set only through the host     
640275 
 
4. There are two pages of “Settings”. Shift page by using “
” or “
”, and select 
the parameter by using “
” or “
”. Press “ENT” to confirm.   
As shown in the above figure, the monitoring module divides the parameters to be 
set into 6 kinds: alarms parameter, battery parameter, AC parameter, DC parameter, 
rectifier parameter and system parameter.   
Among which, the battery parameters are divided into 5 kinds: basic, BLVD, 
charging management, battery test, temperature coefficient, and they are displayed 
in two pages, as shown below: