Chapter 7  Troubleshooting      75 
ACTURA Flex 48330
 
Power System  User Manual 
Chapter 7  Troubleshooting 
7.1  Troubleshooting Rectifier 
1. Troubleshoot Rectifier according to LED Indication 
The usual fault symptoms of the rectifier include: power indicator (green) off, 
protection indicator (yellow) on, protection indicator (yellow) blinking, alarm 
indicator (red) on, and alarm indicator (red) blinking.   
Table 7-1  Troubleshooting 
Symptom 
Cause 
Suggestion  
No input voltage   
Make sure there is input voltage   
Power indicator (green) off 
Input polarity reversed or input fuse 
blown 
Replace the fuse with a new one of the same 
model or reconnect the input power with 
correct polarity.   
AC input voltage outside the normal 
range 
Ensure the AC input voltage remain within 
normal range   
PFC over-voltage 
Replace the rectifier 
Current sharing function is disabled 
Replace the rectifier 
Rectifier over-temperature protection, which is caused by: 
1. Fan blocked 
1. Remove the obstacle that blocks the fan   
2. Ventilation blocked: the inlet or 
outlet blocked 
2. Remove the objects that blocks the inlet or 
outlet 
3. Ambient temperature too high or 
rectifier inlet too close to an heater 
3. Remove the heater, lower the ambient 
temperature  
Protection indicator (yellow) 
on 
Rectifier not inserted into the slot 
completely  
Insert the rectifier again properly 
Protection indicator (yellow) 
blinking 
Rectifier communication failure 
Check the communication cables 
Alarm indicator (red) on 
Rectifier over-voltage 
Remove the rectifier from the DC power 
system, restart the rectifier, and replace the 
rectifier if over-voltage still occurs. 
Alarm indicator (red) blinking    Fan not running   
Replace the fan 
 
2. Rectifier Current Sharing Unbalanced 
When multiple rectifiers are in parallel connection and the unbalance of current 
sharing among them is bigger than 3%, check if the communication cables are 
correctly connected.