4.2
Module LED Indication
Every Battery, Power and Control Module features two LEDs to help inform the user of the module 
status, as shown below left. Refer to Table 2 for details.
Table 2
Guide to LEDs
Status 
LED
(Green)
Fault
LED
(Yellow)
Module Status
OFF
OFF
Module not inserted into 
frame. System is OFF.
OFF
ON
Module is initializing
(max 30 seconds*).
FLASHING
OFF
Normal Operation
FLASHING
FLASHING
Module is in start-up 
qualification mode or module 
warning. **
FLASHING
ON
Module failed and is off-line.
OFF
FLASHING
Abnormal operation, 
re-insert module. 
If this persists, contact 
Liebert Global Services at 
1-800-543-2378.
ON
OFF
ON
ON
ON FLASHING
* If this persists for more than 30 seconds, check to verify the 
lever is in the down position, otherwise the module is faulty.
** If both green and yellow LEDs are flashing for more than 30 
seconds, then reinsert module.
Green Status LED
Yellow Fault LED
Control Module
Green Status LED
Yellow Fault LED
Green Status LED
Yellow Fault LED
Battery Module
Power Module