Chapter 3. Making Electrical Connections 
Page 29 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
DC Load Distribution Electrical Connections to List 21-24 DC Load 
Distribution Sub-Rack(s) (if furnished) 
Danger: 
Adhere to the “Important Safety Instructions” presented at the front of 
this document.  DO NOT attempt to work on an energized system. 
Warning:  Check for correct polarity before making connections. 
 
HRMG (High Resistance Midpoint Ground) Configuration 
Load distribution leads are connected to the load distribution devices as shown in Figure 
3-11.
 
 
NPG (Negative Pole Ground) Configuration 
Load distribution leads are connected to the load distribution devices and return busbar 
as shown in Figure 3-11.  Note that the return busbar is connected to ground as 
described in “NPG Configurations Only:  Return Busbar (-Bus) Grounding Connection on 
page 17.