External Maintenance Bypass Cabinets
The bypass cabinet enables maintenance operations and repairs to be performed in full isolation 
while also allowing the disabling of each UPS without affecting the ordinary operation of the system 
(depending on the redundancy level).
The optional maintenance bypass cabinet must be used in all configurations where one internal main-
tenance bypass switch is insufficient to supply the full system load.
Each kVA rating has maintenance bypass cabinets sufficient to supply the full system load up to six 
units in parallel power operation.
4.2
Interlock with UPS Module
Interlock the External Maintenance Bypass Switch with the operation of the UPS module(s) prevents 
backfeed of the External Bypass AC power into the Inverter if an incorrect switching sequence is 
used. A volt-free auxiliary status contact from external bypass switch QF3 is connected to UPS termi-
nal X3 (MBC interface) of the parallel control board (M3).