72/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
7.4.5  Reconnect a Unit to a parallel system 
 
1.  Connect the Utility supply on the separated Unit. 
• 
Press mute, to reset alarm and buzzer
 
 
First operated unit
 
All other units of the system
 
 
 
2. Connect the Battery to the UPS separated by closing the external Battery 
Switch or Fuses.
 
 
 
3.  Close Q1 (Pos. I) on the separated Unit. 
Rectifier starts automatically.
 
 
 
First operated unit
 
All other units of the system
 
 
 
4. Press inverter on ( I ) key on the separated Unit. 
After Soft-start of the Inverter, the Inverter connects automatically to the other Units 
of the parallel system.
 
 
 
First operated unit
 
All other units of the system
 
 
 
End of procedure