20/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
5 CONTROL 
PANEL 
 
5.1 CONTROL 
PANEL 
 
Fig. 5.1-1   Control Panel
 
 
5.2 
TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL 
 
inverter on/off
 
Key to switch the Inverter ON. 
(This key is also used to reset total off if pressed simultaneously with total 
off
 push button). 
 
 
inverter on/off
 
Key for Inverter shutdown
Press key to transfers the Load to Utility
Keep pressed for 5 seconds to shutdown the Inverter
This key is also used as the EPO (Emergency Power Off) reset. 
 
 
mute
 
Key to reset general alarm and buzzer. 
 
 
test
 
Key to test the control panel LED’s and buzzer. 
(Pressing this key causes all the LED’s to light and the buzzer to
sound 3 times). 
 
 
The push-button total off is protected by a red cover. 
By pressing it, you immediately separate the UPS from utility and the Load
 
Attention:  total off cannot disconnect the UPS from the Load with Q2 
closed
. 
 
To reset total off: push and hold the total off push-button and the I key 
(inverter on) simultaneously for some seconds.
 
  For parallel system, pressing total off on one unit connected on 
parallel bus (switch Q1 closed), all the units are separated from the load
The “total off” reset must be done only on one unit connected on the parallel 
bus (switch Q1 closed).
 
 
 
Special care must be taken in using this command, in order to 
avoid accidental Load
 disconnection.