AEG Protect 1.150 User Manual
31
♦ Mount the connection cover of the cable clamping unit.
5.2.2
Connection Cross-Sections and Fuse Protection
The required dimensions can be found in the following table:
The required dimensions can be found in the following table:
PROTECT
1.100
PROTECT
1.150
1.150
*
PROTECT
1.200
1.200
*
Max. current consumption
(bypass)
(bypass)
46A 68A 91A
Incoming mains cable
(UPS input)
(UPS input)
min.
max.
max.
10 mm²
16 mm²
16 mm²
16 mm²
35 mm²
35 mm²
25 mm²
35 mm²
35 mm²
Load connection
(UPS output)
(UPS output)
min.
max.
max.
10 mm²
16 mm²
16 mm²
16 mm²
35 mm²
35 mm²
25 mm²
35 mm²
35 mm²
Battery connection
Via
enclosed
battery
connection
cable
protected
against
polarity
reversal
enclosed
battery
connection
cable
protected
against
polarity
reversal
Min. 16 mm², Max. 35 mm²
per terminal
Battery connection cable is
included with the battery unit
Observe earth-fault- and
short-circuit-proof routing!
Mains fuse (UPS input)
50A gl
80A gl
100A gl
When using line safety switches, observe
trigger characteristic: “D”
trigger characteristic: “D”
Line safety switch “B” characteristic
Load fuse
(recommended max.)
(recommended max.)
16A
20A
25A
* To ensure a reliable strain relief, individual wires must be laid
especially for connecting the 15 and 20 kVA UPS systems.
especially for connecting the 15 and 20 kVA UPS systems.
Recommended connection cable acc. to VDE 0298-4:
Specially for 15 and 20 kVA:
Special rubber-insulated wire
NSGAÖU or NSGAFÖU
or NYY or
Radox 4GKW-AX
e.g. Huber & Suhner
NSGAÖU or NSGAFÖU
or NYY or
Radox 4GKW-AX
e.g. Huber & Suhner
Alternatively, the 10 kVA UPS system can also be connected
via a multi-wire rubber-sheathed cable.
via a multi-wire rubber-sheathed cable.