general characteristics of Galaxy PW™ UPS
UPS power rating in kVA
100
130
150
180
200
225
Normal AC input
number of conductors
3 phases
rated voltage and tolerances
480 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances
60 Hz / ± 10%
THDI
< 14%
< 11%
< 10%
< 8%
< 7.6%
< 7.5%
power factor
up to 0,9
Bypass AC input
number of conductors
3 phases         3 phases + neutral
rated voltage and tolerances
480 V / ± 10%
rated frequency and tolerances
60 Hz / ± 10%
Load
number of conductors
3 phases         3 phases + neutral
Ph/Ph voltages
480 V
Ph/N voltages
277 V 
voltage fluctuations
± 1%
adjustable frequency and tolerances 
(on battery power)
60 Hz ± 0,05 Hz
synchronization with bypass
± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)
voltage variation for 0 to 100% load step change
± 2% (with battery)
permissible overloads
150% for 1 minute, 125% for 10 minutes
Isc Ph/Ph (% of I rated)
4.7
3.6
3.2
2.6
2.4
2.1
Isc Ph/N (% of I rated)
7.4
5.7
5
4.1
3.7
3.3
THDU Ph/Ph and Ph/N for linear load
< 1,5% Ph/Ph, < 2% Ph/N
THDU Ph/Ph and Ph/N for non-linear load
< 2% Ph/Ph, < 3% Ph/N
(at 80% of Pn)
Battery
standard battery type
gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW)
100
130
150
180
200
225
efficiency at 50% load (%)
90.5
91
92
92.5
92.5
93
(values ± 1%)
efficiency at 100% load (%) 
92.5
93
93
93
93.5
93.5
(values ± 1%)
heat losses  (1)
in KW
8.1
9.8
11.3
13.5
13.9
14.1
in cal./s
1940
2350
2700
3240
3340
3380
storage temperature range
-25 °C to +70 °C
operating temperature range
0 °C to 35 °C (40 °C for 8 hours)
relative humidity
95% maximum
maximum operating altitude without derating
< 1000 meters
noise level (dBA)
62
63
64
65
67
68
dimensions  (mm)
width
1215
depth
840
height
1900 ± 10
weight (lbs/kg)
3050/1388
standards
design
NFPA / NEC / NEMA / OSMA
product and safety
UL 1778 - ULC
electromagnetic compatibility
FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.