3. Operations 
Outlet Control 
The Outlet Control section offers access to the Individual and Group outlet control pages.  From the Individual 
and Group pages, the user can review and manipulate power control functions for all outlets and groups 
assigned to the current user.  Both pages include the outlets absolute and descriptive names, the Outlet Status 
reported to the Switched PDU by the outlet, the current Control State being applied by the Switched PDU and 
the outlet load in amperes.   
Available outlet and group power states may be set to on, off or reboot; the reboot operation turns the outlet(s) 
off, delays for a period of 15 seconds and then turns the outlet(s) on. 
Individual 
The Individual outlet control page displays all outlets assigned to the current user.  The user may apply on, off 
or reboot actions to individual, multiple or all accessible outlets. 
To apply actions to individual or multiple outlets: 
In the Individual Outlet Control section, select the desired action from the Control Action drop-down menu for 
each individual outlet to be changed and press 
Apply
To apply an action to all outlets: 
In the Global Control section, select the desired action from the Control Action drop-down menu and press 
Apply
Group 
The Group outlet control page displays all groups assigned to the current user as well as the outlets for each 
group. 
To select a group: 
Select the group name from the drop-down menu and press 
Select
.  The page will refresh to display all outlets 
associated to the selected group name. 
To apply an action to a group: 
Select the desired action from the drop-down menu and press 
Apply
Outlet State/Control State Field Values 
Outlet State   Control State 
Description 
  
On  
On 
Outlet is on 
Off 
Off 
Outlet is off 
Off 
Pend On 
Outlet is off and about to turn on in response to a sequence timer 
Off 
Reboot 
Outlet is off and a Reboot action has been initiated 
On  
Idle On 
A restart has occurred – Last Control State has been maintained 
Off 
Idle Off 
A restart has occurred – Last Control State has been maintained 
On 
Wake On 
A power-loss has occurred – Wakeup State has been applied 
Off 
Wake Off 
A power-loss has occurred – Wakeup State has been applied 
On/Wait 
Off 
Outlet state in transition – Requery of outlet status required 
Off/Wait 
On 
Outlet state in transition – Requery of outlet status required 
On/Error 
varies 
Error State – Outlet should be off but current is sensed at the outlet 
Off/Error 
varies 
Error State – Outlet should be on but no current is sensed at the outlet 
No Comm 
varies 
Communication to the outlet has been lost* 
* Control State will be applied when communication is re-established 
Page 14 - 301-0399-4 Rev A.