4.2 Hot-swapping the power module
 Stop the UPS with the OFF button  18  (press more than 3 seconds).
 Check if UPS is on bypass AC source:
led   15   is on (If led   15   is not on, do not turn the manual bypass and
call the after sales support department).
 Turn the manual bypass switch   7   to the BYPASS position.
 Switch the battery circuit breaker (s)   12   to the "0" position.
 Switch the Normal AC source circuit-breaker   9   to the "0" position and
wait 30 seconds.
 Remove the three fixing screws to free the junction Input/Output box.
 Disconnect the battery cables  28  and  29  from the power module.
The power module can be replaced.
The connected equipment is powered by the Bypass AC source.
18
15
7
Disconnecting the power module
9
29
28
4. Maintenance
This operation can be performed without interrupting the load.