MGE UPS SYSTEMS
AC power
(single-phase +
earth)
30
29
12
26
24
25
output
to load
XB2
XB1
N
N
Ph
Ph
6
7
Pulsar EX with the "manual
bypass" module ("Install"
version)
ensure that the "automatic bypass"
module  21  is properly installed;
take the "manual bypass" module  31 ;
plug the rear connectors into connectors
  and  6  of Pulsar EX (see figure 5);
tighten the module using the 2 screws 24 ;
plug the connecting cable  26  into the
connector  12  of Pulsar EX;
connect the loads having to be supplied
by Pulsar EX:
open the cover protecting the terminal
blocks, pass the cable in the left cable-
clamp and connect the 3 wires (phase,
neutral and ground) to the output terminal
block  29  (XB2).
connect Pulsar EX to the AC supply;
pass the cable in the right cable-clamp
and connect the 3 wires (phase, neutral and
ground) to the input terminal block  30
(XB1) and put back the protective cover;
do not connect the supply cable to the AC
outlet if the battery extension module option
has to be installed, else directly consult the
"operation" section.
Figure 5