reconnecting Pulsar EX
Operating mode:
take the "manual bypass" module  25 or
 31  and connect it behind Pulsar EX;
screw on this module using the 2 screws
 24 ;
plug the cable  26  into the connector  12
on Pulsar EX;
close the battery circuit-breaker  7  on
Pulsar EX (as well as the circuit-breakers
 32  on the Pulsar EXB battery extension
modules if fitted): "l" position;
with the "manual bypass" switch  28  set
to "BY-PASS", depress the button  3  ;
check after 15 seconds that Pulsar EX
has started properly and that the following
indications are obtained:
if the indicator lights are in a status other
than that indicated, do not switch the "manual
bypass" and contact our after-sales service;
switch the "manual bypass"  28  from the
"BY-PASS" position to the intermediate
position (see figure 10).
The following indications are obtained:
1a
to
1c
off
intermittent beeps
!
-
+
%
-
+
1f
flashing
1e
off/power on
1d
flashing/operation on
               "manual bypass"
"manual bypass" switch   28
BY-PASS
NORMAL
"NORMAL" position
BY-PASS
NORMAL
intermediate position
BY-PASS
NORMAL
"BY-PASS" position
1a
to
1d
intermittent beeps
!
-
+
%
-
+
n/a
1f
flashing/load in
              "automatic
              bypass"
1e
off/power on
switch the "manual bypass"  28  from the
intermediate position to the "NORMAL"
position: operation is now normal and the
following indications are obtained:
!
-
+
%
-
+
1a
to
1d
indicate battery state
1f
on/load energized
silence
1e
off/power on
flashing/power off
Figure 10