MGE UPS Systems EX30 User Manual
30
Pulsar EX: 51032306XT/BB
MGE UPS SYSTEMS
AC power
(single-phase +
earth)
(single-phase +
earth)
30
29
12
26
24
25
output
to load
to load
XB2
XB1
N
N
Ph
Ph
6
7
Pulsar EX with the "manual
bypass" module ("Install"
version)
bypass" module ("Install"
version)
c
ensure that the "automatic bypass"
module 21 is properly installed;
c
take the "manual bypass" module 31 ;
c
plug the rear connectors into connectors
4 and 6 of Pulsar EX (see figure 5);
c
tighten the module using the 2 screws 24 ;
c
plug the connecting cable 26 into the
connector 12 of Pulsar EX;
c
connect the loads having to be supplied
by Pulsar EX:
v
open the cover protecting the terminal
blocks, pass the cable in the left cable-
clamp and connect the 3 wires (phase,
neutral and ground) to the output terminal
block 29 (XB2).
clamp and connect the 3 wires (phase,
neutral and ground) to the output terminal
block 29 (XB2).
c
connect Pulsar EX to the AC supply;
v
pass the cable in the right cable-clamp
and connect the 3 wires (phase, neutral and
ground) to the input terminal block 30
(XB1) and put back the protective cover;
ground) to the input terminal block 30
(XB1) and put back the protective cover;
c
do not connect the supply cable to the AC
outlet if the battery extension module option
has to be installed, else directly consult the
"operation" section.
has to be installed, else directly consult the
"operation" section.
Figure 5