Characteristics
(1) values for operation at 50%, 66% and 100% rated output
Catalog numbers
EXtreme 700 C
EXtreme 1000 C
EXtreme 1500 C
Format
Tower
Rack
Tower
Rack
Tower
Rack
UPS
66345
66351
66346
66352
66347
66353
Warranty + for UPS
66813
66813
66818
66818
66818
66818
Pulsar EXB
66348
66354
66349 
66355
66350 
66356
Warranty + for Pulsar EXB
66813
66813
66813
66813
66813
66813
Pulsar EXtreme 1500 transformer
66357
Pulsar EXtreme 1500 CLA
66359
66358
Warranty + for Pulsar CLA
66818
66818
slot for a communication
card
RS232 and USB communications ports 
2 programmable outlets
AC input connector
ON/OFF
operation on bypass, in ON-LINE mode 
or on battery
status of programmable outlets 1 and 2
lamp test or buzzer off 
forced transfer to and from bypass
press and hold to display percent load
alarm and battery level indicators 
connectors for Pulsar EXB battery 
extension modules
Pulsar EXtreme
700 C
1000 C
1500 C
General
Power (Pn)
700 VA / 490 W
1000 VA / 700 W
1500 VA / 1050 W
Input-voltage range
120/140/160 to 276 volts without using battery power (1)
Frequency range
50/60 Hz (auto-selection)
Power factor (THDI)
>0.95 (< 5%)
Sinusoïdal output voltage
200/208/220/230/240 Volts
Harmonic distortion
<4% on linear load, <6% on non-linear load
Efficiency 
85%
87%
88%
Crest factor
3:1
3:1
3:1
Short circuit current (A)
25
29
29
Overload capacity (Online mode)
110% permanent, 130% 12s, >130% 1.5s
Batteries
Backup time
100% Pn 
50% Pn
100% Pn
50% Pn
100% Pn
50% Pn
Standard
7
14
7
17
6
19
Pulsar EXtreme C + 1 Pulsar EXB        
24
47
27
59
24
79
Pulsar EXtreme C + 2 Pulsar EXB           
41
82
47
93
43
119
Pulsar EXtreme C + 3 Pulsar EXB         
53
124
64
136
62
168
Automatic battery test
Yes, at regular intervals without risk of interrupting protected applications
Communicatio
n
USB port 
yes
yes
yes
RS232 port 
yes
yes
yes
Optional cards 
SNMP card
status information card
Environment
Acoustic noise
<
40 dBA
Operating temperature
0 to 40°C
Standards and certifications
Performance
EN 50091-3/IEC 62040-3
Safety
EN 50091-1, EN 60950 (RD/), IEC 60950
EMC   
EN 50091-2/IEC 62040-2, EN 55022/B, FCC 47 part 15 - Subpart B - Class A,
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3
Marking and certifications
CE,TÜV/GS, UL, cUL, C-Tick
Design and manufacture
ISO 9001
Dimensions 
(HxWxD in mm)
and Weight 
(Kg)
UPS (electronics + battery)
Tower 
235.5x145x400
235.5x145x400
235.5x145x505
Rack
88(2U)x482.6x430
88(2U)x482.6x430
88(2U)x482.6x493
Electronics module
Tower/Rack
10/14
12/16
15/20
Battery module Pulsar EXB
Tower/Rack
11.5/17
15/21
21/27.5
CLA module (without batteries)
Tower/Rack
8.5/11.5
Warranty
2 years, extendable by contract
automatic recognition of 
battery extension modules
As 
standar
ds, 
specifications 
a
nd 
designs 
c
hange 
fr
om 
time 
to 
time, 
p
lease 
ask 
for 
c
onfirmation 
of 
the 
information 
given 
in 
this
 publication. 
All 
the 
trademarks 
quoted 
b
elong 
to 
their 
respective 
owners. 
Publication: 
MGE 
U
PS 
SYSTEMS, 
1
1
 2000
P
ro
d
u
ction: 
SYL
V
AIN 
Illustrations: 
Lucy 
in 
the 
Sky
ADN 
Communications.