2. Installation
Module 425 mm deep
2. Install the rear base panel  23  (not
mandatory).
3. Position the module.
4. Level the module using the adjustable feet
24 .
5. Attach the module to the wall using the
two rear brackets.
6. Install the base panels  23  on the sides
and front.
7. Remove the bracket  26  on the top of the
module  (used only for back-to-back
assembly of two modules) and retighten the
fixing screw.
Connection cables run under the false floor
or in a trough.
Important:
At least 400 mm of free space is required
above the module to ensure correct
ventilation.
At least 720 mm of free space is required
in front to open the doors.
24
Footprint of module
Force exerted on the floor by the four feet:
 28 kg/cm
2
.
Rear of module
Front of module
4 feet, diameter 40 mm
Installation against a wall
Caution: during handling, make sure the module does not fall over.
1. Turn to horizontal position the two
brackets  25  at the back used to secure the
module (see figure).
25
26
23
23
23
24
69.5
69.5
67
67
82
82
1076
276