3. Operation
3.1 Turning on the PMM module
1. Close the upstream switching device (external and not supplied) on the circuit supplying the PMM module.
2. In a module with an isolation transformer, close ("I" or ON position) circuit breaker Q1  5   (see page 7) .
3. Make sure disconnector-fuses F1 and F2 are closed and close ("I" or ON position) circuit breaker Q2  5   (see page 7) .
 The system status LED  17  (see page 8) flashes yellow a few seconds, then green and should subsequently remain
green.
 After a few seconds, the first page of measurements is displayed:
3.2 Display
4. Close the circuit breakers on the output circuits to be powered.
Metering mode
Alarm    mode
Setup    mode
The display unit for the PMM module offers three operating modes:  metering, alarm and setup.
This is the default mode.
Ph-A     CH01     0.000
BCM
     CH02     0.000
BCM 
    CH42     0.000
Ph-B     CH25
             WARNING
UP
Ph-C     CH12
             ALARM
METER
SELECT
+
UP
GENE      OVER
MCM 
       VOLTAGE
UP
UP
GENE      OVER
MCM  
      CURRENT
UP
AUX   INPUT
ALARM
Enter Password :
* * * * * *
DOWN
UP
View System Info
Find Meters
Review Meters
+
UP
DOWN
SELECT
DOWN
SELECT
UP
UP
UP
Setup
Communication
UP
Setup
Operation
UP
UP
Ph-A     CH01     0.000
BCM
     CH02     0.000
GENE    KWH    0000.0
MCM 
    KW       0000.0
METER
DOWN
UP
METER
BCM 
    CH42     0.000
Ph-B     CH01     0.000
BCM 
    CH02     0.000
DOWN
UP
METER
BCM
     CH42     0.000
Ph-C     CH01     0.000
BCM 
    CH02     0.000
DOWN
UP
METER
SELECT
SELECT
SELECT
MCM 
    MAX    0000.0
DOWN
UP
METER
METER