Table 1-2: Inverter Module Dimensions.
Inverter Module
HEIGHT (in/cm)
DEPTH (in/cm)
WIDTH (in/cm)
WEIGHT (lb/kg)
64004-9MSK1
5.18 / 13.16
15.12 / 38.4
15.76 / 40.03
46 / 20.86
Note:  Weight:  Six-mod receiver = 135 lbs. (61.2 kg)   1 UPS Module  =  46 lbs. (20.09 kg) 
Total System Weight, 21 kVA system = 411 lbs. (186.4 kg)
1.3
Electrical Specifications
Electrical Specifications are subject to revision without notice.
1.3.1
DC Input
Nominal:  -48Vdc; Operating Range:   -39.5Vdc to -57 Vdc 
NOTE:
An external DC circuit breaker or fuse should be used at the DC
source.
1.3.2
AC Output (per module)
Voltage:
120Vrms
or
240Vrms
Current:
25Arms
or
12.5Arms
Frequency:
60Hz
or
50Hz
Ta b l e   1 - 3 :   S 4  A C   O u t p u t   C u r r e n t   R a t i n g s .
Attention: Watts rating = 85% of the VA rating at 120/240 VAC.
MAXIMUM OUTPUT RATINGS
7 KVA unit
14 KVA unit                       
21 KVA unit
Vout Iout
Output 
Output 
Iout  Output 
Output
Iout Output 
Output 
(Vac)
(A)
Power
VA
(A)
Power
VA
(A)
Power
VA
(W)
(VA)
(W)
(VA)
(W)          (VA)                
110
58.33
6000
6416
116.66
12000
12833
175
18000
19250
115
58.33
6000
6708
116.66
12000
13416
175
18000
20125
120
58.33
6000
7000
116.66
12000
14000
175
18000
21000
208
29.165
6000
6066
58.33
12000
12133
87.5
18000
18200
220
29.165
6000
6416
58.33
12000
12833
87.5
18000
19250
230
29.165
6000
6708
58.33
12000
13416
87.5
18000
20125
240
29.165
6000
7000
58.33
12000
14000
87.5
18000
21000
Units configured to other then 120/240VAC are derated due to current limit.
The % Load reading on the display panel is always with reference to the 120/240 Vac WATT and VA ratings.