MGE UPS Systems 3000 RT 3U User Manual

Page of 24
34007776EN/AB
 - Page 11
2. Installation
2.5 Connections with a FlexPDU (Power Distribution Unit) module (optional)
  
2.6 Connections with a HotSwap MBP module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads 
(HotSwap function).
  
 
1 - Connect the UPS socket (10) to the AC-
power source using the cable (31) supplied.
2 - Connect the input socket on the FlexPDU 
module (48) to the UPS outlet (7) using the 
cable (41) supplied. The cable and the 
connectors are marked in red.
3 - Connect the equipment to the outlets (45), 
(46)
 and (47) on the FlexPDU module. These 
outlets differ, depending on the version of the 
FlexPDU module.
4 - Fit the connection securing system that 
prevents the plugs from being pulled out 
accidentally.
 
1 - Connect the input socket (56) on the 
HotSwap MBP module to the AC-power 
source using the cable (31) supplied.
2 - Connect the UPS input socket (10) to the 
"UPS Input" (55) on the HotSwap MBP 
module, using the cable (44) supplied. These 
cables and the connectors are marked blue.
3 - Connect the UPS outlet (7) to the "UPS 
Output" (54) on the HotSwap MBP module, 
using the cable (44) supplied. These cables 
and the connectors are marked red.
4 - Connect the equipment to the outlets (49) 
and (50) on the HotSwap MBP module. 
These outlets differ, depending on the 
version of the HotSwap MBP module.
 
Caution. Do not use UPS outlets (8) and (9) 
to supply equipment because use of 
switch (53) on the HotSwap MBP module 
would cut supply to the equipment. It is 
advised not to remove the protective film 
from outlets (8) and (9).
7
8
9
10
48
47
46
45
FlexPDU
41
31
7
8
9
10
By-p
ass
Normal
UPS ON - OK to switch
BY
 P
ASS SWITCH
56
55
49
HotSwap MBP
50
54
53
51 52
44
31