6. Appendices
6.1 Technical specifications
  
  
(1) Depending on the output voltage selected: 200V / 208V / 220V / 230V / 240V, the output power is 
1980VA / 1980VA / 2200VA / 2200VA / 2200VA.
(2) Depending on the output voltage selected: 200V / 208V / 220V / 230V / 240V, the output power is 
2700VA / 2700VA / 3000VA / 3000VA / 3000VA.
(3) Standard output power is 2700 W, 2400 W with an EXB module.
(4) Values for 33% / 66% / 100% of UPS output.
(5) Programmable: 200V / 208V / 220V / 230V / 240V using the UPS Config software.
(6) Frequency-converter mode is programmable using the UPS Config software.
(7) Depending on the output voltage selected: 200V / 208V / 220V / 230V / 240V, the maximum output current is 
9.9A / 9.5A / 10A / 9.6A / 9.2A.
(8) Depending on the output voltage selected: 200V / 208V / 220V / 230V / 240V, the output current is 
13.5A / 13A / 13.6A / 13A / 12.5A.
 
Pulsar M 2200
Pulsar M 3000
Pulsar M 3000 XL
Pulsar M EXB
Output power
2200 VA 
(1)
 / 
1980 W
3000 VA 
(2)
 / 
2700 W 
(3)
3000 VA 
(2)
 / 
2700 W 
Electrical supply network
 Rated input voltage
 Input voltage range
 Frequency
 Power factor
 Leakage current
Single phase 230 V
 110 / 140 / 200 V to 284 V 
(4)
50/60 Hz (autoselection)
> 0.95
< 2 mA
Load output
 Voltage
 Frequency
 Harmonic distortion
 Overload capacity
 Current
Single phase 230 V ±3% 
(5)
50/60 Hz ±0,5% 
(6)
< 4% for linear load, 
< 6% for nonlinear load
102% continuous, 105% 20s, > 130% 1.5s
9.6 A 
(7)
13 A 
(8)
Battery
6 x 12V - 7 Ah, 
sealed lead acid,
maintenance free
6 x 12V - 9 Ah, 
sealed lead acid,
maintenance free
without internal 
battery
Two 6 x 12 V - 9 Ah 
strings, sealed lead 
acid, maintenance 
free
Environment
 Operating temperature range
 Relative humidity
 Storage temperature range
 Altitude
 Noise level
O°C to 40°C
20% to 90% (without condensation)
-25°C to 40°C
1000 m
< 46 dBA
< 50 dBA