4. Access to measurements and personalisation data
Output personalisation  
(1) These parameters may be modified only when the UPS is OFF.
Detailed comments are available in the Personal Solution-Pac software.
ON/OFF personalisation  
Battery personalisation  
4.4 Personalisation using external software
  
Function
Factory setting
Other available settings
Comments
Output voltage 
(1)
230 Volts AC
200/208/220/240 Volts AC
Frequency converter 
(1)
Disabled
Enabled
The connected devices are never 
transferred to the bypass.
Output frequency 
(1)
Automatic selection
50 or 60 Hz
User selectable only if the 
frequency-converter function is 
enabled.
Transfer to the bypass AC 
input 
(1)
Bypass AC power must 
be within tolerances
Bypass AC power may be 
outside tolerances
Overload level 
(1)
102%
50 / 70%
Alarm if threshold is overrun.
Function
Factory setting
Other available settings
Comments
Start on battery power
Enabled
Disabled
Automatic restart
Enabled
Disabled
The UPS restarts automatically when 
AC power returns.
Energy savings
Disabled
Enabled
When function enabled, battery shuts 
down when power drops to <5%.
Detection of phase/
neutral inversion (SWF)
Disabled
Enabled
When function enabled, the UPS 
remains OFF if the system detects 
phase/neutral inversion.
Function
Factory setting
Other available settings
Comments
Battery test
Weekly test
No test / daily test / 
monthly test
Low-battery warning
20%
0 to 100%
Adjustable in 1% steps.
Selection of the backup 
time
Automatic detection of 
number of battery 
modules
65 to 400 Ah
Battery protection against 
excessive discharges
Enabled
Disabled
When function disabled, MGE UPS 
SYSTEMS warranty no longer 
applies.
  
  Insert the Solution-Pac CD-ROM in the drive.
  On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal 
Solution-Pac software.
  Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.