MGE UPS Systems 2200 RT 3U User Manual

Page of 24
34007776EN/AB
 - Page 20
5. Maintenance  
  
Mounting the new battery module
Carry out the above instructions in reverse order.
  
5.3 Maintenance on a UPS equipped with the HotSwap MBP module  
  
 
D - Remove the metal protection cover in 
front of the battery (two screws).
  
  
E - Pull the plastic tab to remove the battery 
block and replace it.
  
 To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS.
 Take care to firmly press together the two parts of the connector during remounting.
 The 
HotSwap MBP module makes possible 
to service or even replace the UPS without 
affecting the connected loads (HotSwap 
function).
Maintenance: 
1 - Set switch (53) to the Bypass position. The 
red LED on the HotSwap MBP module goes 
ON, indicating that the load is supplied 
directly with AC power.
2 - Stop the UPS by pressing the ON/OFF 
button (27) on the UPS control panel. LED 
(51) "UPS ON - OK to switch" goes OFF, the 
UPS can now be disconnected and replaced.
Return to normal operation:
1 - Check that the UPS is correctly connected 
to the HotSwap MBP module.
2 - Start the UPS by pressing the ON/OFF 
button (27) on the UPS control panel. LED 
(51) "UPS ON - OK to switch" on the 
HotSwap MBP module goes ON (otherwise, 
there is a connection error between the 
HotSwap MBP module and the UPS).
3 - Set switch (53) to the Normal position. The 
red LED on the HotSwap MBP module goes 
OFF.