 - Page 13
Ue/In/Eing  230V/10A Max
1
2
Us/Out/Ausg   I max 10A
2.4 Connecting the protected equipment
Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to
the actual electrical consumption of all the equipment to be connected to the UPS.
1 - Remove the power cord supplying the
equipment to be protected.
2 - Pulsar Evolution 2200: Connect the
power cord 
(1)
 just removed from the
equipment to the AC-power socket  11  and
then to the AC-power wall outlet.
Pulsar Evolution 3000/3000 XL: Connect
the supplied power cord  24  (250 V, 16 A) to
the AC-power socket  11  and then to the
AC-power wall outlet.
3 - Connect the protected equipment to the
UPS using the two cords  25  . It is advised
to connect priority loads to the four standard
outlets   8   and any non-priority loads to the
four programmable outlets   9   (in groups of
two outlets).
If the UPS is connected to a
computer running MGE
communications software, it is
possible to program the
interruption of power to the
programmable outlets   9   during
operation on battery power, thus
reserving backup power for the
priority loads.
4 - Lock the connections using the securing
system  29 .
25
8
9
1
2
2. Installation
11
29
As soon as the UPS is energised, the battery begins charging. Eight hours are required to charge to the full rated
backup time.
Pulsar Evolution 3000 XL: At least one EXB additional battery module must be connected to the UPS because it does not
have internal batteries. See the EXB battery-module installation manual (Doc. no. 3400711600) for information on making
the connections.
(1) Make sure the cord has the following
characteristics: 250 V, 10 A, cross-sectional area 1
mm
2
, type HO5.