5. Maintenance
Mounting the new battery module
Carry out the above instructions in reverse order.
  
5.3 Maintenance on a UPS equipped with the HotSwap MBP module 
5.4 Training centre
  
  
 To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS.
 Take care to firmly press together the two parts of the connector during remounting.
 The 
HotSwap MBP module makes it 
possible to service or even replace the UPS 
without affecting the connected loads 
(HotSwap function).
Maintenance 
1 - Set switch (53) to Bypass position. The red 
LED on the HotSwap MBP module goes ON, 
indicating that the load is supplied directly 
with AC input source power.
2 - Stop the UPS by pressing the ON/OFF 
button (24) on the UPS control panel. LED 
(51) "UPS ON - OK to switch" goes OFF, the 
UPS can now be disconnected and replaced.
Return to normal operation
1 - Check that the UPS is correctly connected 
to the HotSwap MBP module.
2 - Start the UPS by pressing the ON/OFF 
button (24) on the UPS control panel. LED 
(51) "UPS ON - OK to switch" on the 
HotSwap MBP module goes ON (otherwise, 
there is a connection error between the 
HotSwap MBP module and the UPS).
3 - Set switch (53) to Normal position. The red 
LED on the HotSwap MBP module goes 
OFF.
  
To fully master operation of your MGE UPS SYSTEMS product and carry out level 1 servicing, see our complete range of 
technical training courses, available in both French and English.
50 Hz training centre
MGE UPS SYSTEMS
140 avenue Jean-Kuntzmann
Zirst - Montbonnot St-Martin
38334 St-Ismier Cedex     FRANCE
Tel. +33 (0)4 76 18 34 14
Fax +33 (0)4 76 18 45 21
training@mgeups.com
 www.mgepowerlearning.com
(Catalogue and registration available on line)
60 Hz training centre
MGE UPS SYSTEMS
1660 Scenic Avenue
Costa Mesa CA     92626 USA
Tel. +1 714 557 1637
Fax +1 714 437 9072
technical.training@mgeups.com
 www.mgepowerlearning.com
(Catalogue and registration available on line)
7
8
9
10
By-pass
Normal
UPS ON - OK to switch
BY
 P
ASS SWITCH
56
55
49
HotSwap MBP
50
54
53
51 52
44
31