4. Maintenance
4.2 UPS replacement
Fault-tolerant connection module
Before carrying out this operation, the supply of power to the connected equipment must be cut.
The equipment will therefore no longer be powered.
Disconnection:
1. Shut down the UPS by pressing button       (return to the OFF
position).
2. Open the battery circuit breaker(s)      .
3. Open the upstream device (OFF position) controlling the
supply of AC power to the UPS.
4. Remove the two fixing screws       and the connection module
from the UPS.
Reconnection:
1. Insert the connection module in the connector       and secure
using the two screws       .
2. Close the upstream device (ON position) controlling the
supply of AC power to the UPS.
3. Close the battery circuit breaker(s)      .
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
4. Start the UPS by pressing button      .
The connected equipment is again protected by the UPS.