Powerware 650825 kVA User Manual

Page of 192
UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
 9395 UPS (650–825 kVA) Installation and Operation Manual  
S
  164201725 Rev 2 www.powerware.com
3−10
Table 3-5. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825 
– Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
585
650
591
750
675
750
682
825
742
825
750
Input and Output Voltage
Volts
400/400
480/480
400/400
480/480
400/400
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1079
891
1245
1028
1369
1130
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
DC Input from Each Battery Disconnect to Each UPS
UPM
(1) Positive, (1) Negative
C
Amps per UPM
551
551
551
551
551
551
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
350
(3)
500
(5)
500
(3)
500
(5)
500
(4)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
NOTE  Callout letter 
A
B
C
, and 
D