APC SMC1000 User Manual

Page of 15
Smart-UPS C  1000/1500 VA  120/230 Vac  Tower
8
System Faults
Feature Reference Guide
1000/1500 120 Vac
1000/1500 230 Vac
P00
Output Overload
P01
Output Short Circuit
P02
Output Over Voltage
P04
Unit Over Temperature
P06
AVR Relay Fault
P13
Inverter Fault
Note: Refer to the "Feature Reference Guide" on page 8 for a detailed description of the front panel buttons and icons.
For more information on System Faults, contact customer support at the APC Web site, www.apc.com/support.
Function
Button
Timing 
(seconds)
UPS 
Status
Description
Power
Power On
0.2
Off
Press the 
POWER
 
ON
/
OFF
 button to turn on the UPS. The UPS will operate 
on AC power.
If AC power is not available the UPS will operate on battery power.
Power Off
2
On
Press the 
POWER
 
ON
/
OFF
 button to turn off the UPS. 
Display
Status Inquiry
0.2
On
Press to verify the status or condition of the UPS. The LCD will illuminate 
for 60 seconds.
Power Saving 
mode 
Continuous 
Illumination
2
On
The LCD will illuminate and the UPS will beep to confirm Continuous 
Illumination
 mode is activated. 
The LCD will extinguish and the UPS will beep to confirm that 
Power Saving mode is activated. While in Power Saving mode, the LCD 
will illuminate if a button is pressed or an event occurs, then extinguish after 
60 seconds of no activity.
Mute
Event Specific
0.2
On
Disable any audible alarms caused by an event.
Enable/Disable
2
On
Enable or disable the audible alarms. The Mute icon will illuminate and the 
UPS will beep once. The Mute feature will not activate unless the UPS is 
operating on battery power.
Sensitivity
6
Off
The Load Capacity icon will flash to indicate the UPS is in Program mode. 
Use the 
POWER
 
ON
/
OFF
 button to scroll through and select Low, Medium, 
and High sensitivity levels. The UPS will beep to confirm the selection. 
Refer to Sensitivity adjustment settings on page 4 in this manual.
Self-Test
2
On
The UPS will automatically run a self-test of the internal battery when the 
UPS is turned on.
A manual self-test can be run at any time while the UPS is operating.
Press and hold the 
MUTE
 button, then press the 
DISPLAY
 button for 2 
seconds until the system emits a short beep to indicate the UPS has started a 
Self-Test.
Event Reset
0.2
On
When the Event screen is visible, press and hold the 
DISPLAY
 button, then 
press the 
POWER
 
ON
/
OFF
 button to clear the AC failure event counter.
Fault Reset
2
Fault
After a fault has been identified, press the 
POWER
 
ON
/
OFF
 button to remove 
the visual indication and return to standby status.