APC SMX1000 VA User Manual

Page of 21
Smart-UPS X  750/1000/1500 VA  120/230 Vac  Rack-Mount 2U
8
Controllable Outlet Groups
Overview
The rear panel of the UPS has multiple outlets, some are grouped into Controllable Outlet Groups, all of the other 
outlets are the UPS outlets, which function as an outlet group. All of these groups can independently turn off, turn 
on, shut down, and reboot connected equipment.
The Controllable Outlet Groups can be commanded to do the following:
•  Turn off: Disconnect from power immediately and restart only with a manual command
•  Turn on: Connect to power immediately
•  Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power 
becomes available
•  Reboot: Shut down and restart
In addition, the Controllable Outlet Groups and the UPS outlets can be configured to do the following: 
•  Turn on or off in a specified sequence
•  Automatically turn off or shut down when various conditions occur
Note:
 If the Controllable Outlet Groups are not configured, all of the outlets on the unit will still 
provide battery backup power.
Transfer 
Sensitivity
High
High, Low, Medium
Select the level of sensitivity to power events that the UPS 
will tolerate.
• High: The UPS will go on battery power more often to 
provide the cleanest power supply to the connected 
equipment.
• Low: The UPS will tolerate more fluctuations in power 
and will go on battery power less often. 
If the connected load is sensitive to power disturbances, set 
the sensitivity to High.
Low 
Battery 
Warning
150 sec
Set the value in seconds
The UPS will emit an audible alarm when the remaining 
runtime has reached this level.
Date of 
Last 
Battery 
Replaceme
nt
Date set at factory
Reset this date when the battery module is replaced.
Audible 
Alarm
On
On/Off
The UPS will mute all audible alarms if this is set to Off or 
when the display buttons are pressed.
Battery 
Self-Test 
Interval 
Setting
On start up and every 
14 days since the last 
test
• Never
• Start up only
• Frequency of test (days) The interval at which the UPS will execute a self-test.
Reset to 
Factory 
Default
No
Yes/No
Restore the UPS factory default settings.
Function Factory Default
Options
Description