APC MW II User Manual

Page of 40
Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001
18
AC Input
DC Input
Caution: Over-current protection for the battery circuit is required by code. The minimum 
DC voltage rating of the battery supply over-current protection device is 500 V.
AC Input
Input rating
1200 kW/kVA
Power Factor
1
Input Voltage
380 V
Input Frequency
50 Hz
Nominal input current (note 1)
1698 A
Input Current Limitation (note 2)
2133 A
Input Voltage
400 V
Input Frequency
50 Hz
Nominal input current (note 1)
1793 A
Input Current Limitation (note 2)
2200 A
Input Voltage
415 V
Input Frequency
50 Hz
Nominal input current (note 1)
1728 A
Input Current Limitation (note 2)
2170 A
DC Input
Nominal Voltage (note 3)
2 x 384 V
INom Discharge (note 4)
1628 A
IMax Discharge (note 5)
1929 A