2. Installation
Required cable sizes
   
 
Cable sizes are determined for copper conductors (for aluminium conductors, increase the size by 30%). Size 
calculations also take into account a voltage of 400 V and grouping of four cables.
UPS power 
rating
Minimum sizes for 
separate Normal AC 
input copper cables 
(<100 m)
Minimum sizes for 
separate Bypass 
AC input copper 
cables (<100 m)
Minimum sizes 
for common 
bypass and 
Normal AC input 
copper cables 
(<100 m)
Minimum sizes 
for copper load-
circuit cables 
(<100 m)
Battery/terminal 
connection 
(<15 m)
20 kVA
10 mm
2
16 mm
2
16 mm
2
16 mm
2
16 mm
2
30 kVA
16 mm
2
16 mm
2
16 mm
2
16 mm
2
25 mm
2
40 kVA
16 mm
2
16 mm
2
16 mm
2
16 mm
2
35 mm
2
60 kVA
25 mm
2
25 mm
2
25 mm
2
25 mm
2
70 mm
2
80 kVA
50 mm
2
50 mm
2
50 mm
2
50 mm
2
95 mm
2
100 kVA 
50 mm
2
70 mm
2
70 mm
2
70 mm
2
2 x 50 mm
2
120 kVA 
70 mm
2
70 mm
2
70 mm
2
70 mm
2
2 x 70 mm
2
Connections are made to pre-drilled terminals. 
Hole diameter: 6.5 mm (8.5 mm for 120 kVA).
Earthing cables connect to the earthing plate.
Hole diameter: 6.5 mm (8.5 mm for 120 kVA).