APC 5000 User Manual

Page of 68
34001813EN/AE
 - Page 32
2. Installation
Parallel configuration for increased capacity (maximum four UPS units) 
Interconnections with the external bypass 
cabinet
 Interconnect terminals 1, 3 and 5 on the 
auxiliary terminal block in the cabinet.
 Create a loop between the cabinet and the 
UPS units for terminals 1, 2, 4 and 6 on the 
auxiliary terminal block in the cabinet. The 
order for the XMS04 and XMS05 connectors 
in each UPS unit, from right to left, is 
common, Q3BP, Q4S and Q5N.
Details of terminal blocks (11)
Note. The interconnection cables for the 
external bypass cabinet are not supplied 
(size 2.5 mm
2
 maximum).
Exchange-current interconnections (10):
Use the XMS02 and XMS03 connectors to 
create a loop between the UPS units (all the 
XMS02 and XMS03 connectors must be 
used).
CAN // interconnections (12):
Daisy-chain the UPS units using the XMS06 
and XMS07 connectors. Fit a blue plug on the 
first UPS unit and a red plug on the last unit 
(all the XMS06 and XMS07 connectors must 
be used).
  
 
Note. The supplied cables are ten meters 
long.
To ensure sufficient isolation of 
exchange-current, CAN and external 
bypass cabinet cables, they must be run 
separately from the power cables
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
Q3BP
Q4S
Q5N
2 3 4 5 6
1
11
11
11
11
UPS 2
UPS 1
UPS 4
UPS 3
External bypass cabinet
Jumpers connected to 
aux. terminal block of 
external bypass cabinet
(if necessary)
Blue 
plug
Red
plug
XMS 04 / XMS 05
Q4S
Q3BP
Q5N
Co
mmo
n
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
XMS02   XMS03
XMS06   XMS07
XMS04 XMS05
CAN //
10
10
12
12
10
10
12
12
UPS 1
UPS 2
UPS 4
UPS 3
Blue 
plug
Red plug