APC Power Supply User Manual

Page of 46
InfraStruXure Site Planning, Installation, Start-Up
17
Connect User Contact Inputs and Output 
Relays to the User Connection Plate
Overview 
Make contact closure connections (NO 
or NC) at the user connection plate to 
monitor dry contacts. You can make 
eight connections—four contact inputs 
and four output relays.
The figure at the right shows the location 
of the user connection plate on the roof 
of the PDU enclosure. 
You can make connections from inside 
the enclosure, or you can remove the 
user connection plate and make your 
connections.
Remove the plate using a Phillips or 
standard screw driver to loosen the two 
captive screws. Use the knockout in the 
plate to route cables to and from the user 
connections on the plate. If you remove 
the plate, make sure that you do not 
disturb the existing connections. 
Output relay specifications
Nominal switching capacity: 
1A at 30VDC
Maximum switching power: 
30W
Maximum switching voltage: 
60VDC
Maximum switching current: 
2ADC
Maximum carrying current: 
2ADC
Surge ratings:
2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
1
2
3
4
AT
S E
N
AT
S 0
AT
S
 1
AT
S 2
EPO 
Contact
–     +
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC 
MADE IN USA