APC 4075KVA208V User Manual

Page of 24
Specifications
Environmental Recommendations
Recommended Environment
20° to 25°C (68° to 77°F.); 50% relative humidity; computer room or other
temperature, and humidity-controlled environment
Operating Temperature
0° to 30°C (32° to 86°F) except battery
Storage
-20° to 40°C (-4° to 113°F) except battery
Humidity
Up to 90% non-condensing (operating)
Altitude
Sea level to 3,000 feet without derating
Acoustic Noise
69 dBA at rated load as measured 3 feet from the front of the UPS cabinet.
Electrical Specifications
Output Power Rating (0.8) PF
40 kVA
50 kVA
65 kVA
75 kVA
UPS Voltage (input/output)
208/208
208/208
208/208
208/208
Input/Output Requirements &
Frequency
Three phase, Three wire + N + G, 60Hz
Input Phase Rotation
A,B,C Clockwise
Input Power Factor
>.98
Input Current
102A
127A
166A
191A
Maximum Input Current (at low line
—15%)
120A
150A
195A
225A
Bypass Current
111A
139A
180A
208A
Output Current
111A
139A
180A
208A
Battery Voltage
198 VDC End Voltage 240VDC Nominal 282VDC
Max. Maintenance Voltage
Max. Battery Current at Nominal
Battery Voltage (240 VDC at 100%
load)
157A
196A
255A
294A
Max. Battery Current at Nominal End-
Voltage (198 VDC at 100% load)
190A
238A
309A
357A
Battery Disconnect Circuit Breaker
Rating
250A
400A
Input, Bypass, and Maintenance Bypass
(optional) Switch Rating
150A
250A
Input Fuse Rating
200A
300A
Output Isolation Circuit Breaker Rating
175A
300A
NOTE: Interrupted Transfer to Bypass Source:
If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not more
than 100 msec. in duration).
1. Bypass voltage greater than +15%, —15% from the UPS rated output voltage.
2. Bypass frequency greater than ±2 Hz from the UPS rated output frequency.
990–3964–001
MGE Galaxy 4000 40–75 kVA 208 V
3