APC PDPM150G6F User Manual
19
150/175kw Modular PDU Installation
Specifications
AC Input
Model
PDPM150G6F
PDPM150L6F
PDPM175G6H
Nominal voltage
480V, 3W +G
600V, 3W +G
480V, 3W + G
Frequency
60 Hz
60 Hz
60 Hz
Maximum
continuous
current
continuous
current
180 A
150 A
214 A
Nominal current
178 A
141 A
214 A
Recommended current rating of input circuit breakers
Mains Input
1
(A)
225
200
300
Inrush currents
Inrush Current
2
2000
1500
2100
1
Standard circuit breakers are rated to carry 80% of their current rating
continuously.
2
The supply overcurrent protective device must be able to handle the listed
transformer inrush currents.
AC Output
Model
PDPM150G6F
PDPM150L6F
PDPM175G6H
Nominal voltage
208Y/120V,
3W + N + G
208Y/120V,
3W + N + G
415Y/240V,
3W + N + G
Maximum continuous current
400 A
400 A
243 A
Full load rating
144 kW @ 208V 3
PH
144 kW @ 208V 3
PH
175kW @ 415V 3 PH
Power distribution module
(PDM)
(PDM)
208/120V, 3-pole
modules
208/120V, 3-pole
modules
415/240V, 3-pole
modules
Power distribution poles
available
available
72
72
72
Maximum number of PDMs
24
24
24