APC 6739380EN/JC User Manual

Page of 50
6739380EN/JC - 
Page 41
UPS IMPOSED
TRANSFER DISABLE !
Cannot transfer the load to Main 2 due
to:
transfer conditions not satisfied;
UPS operating on an independent
frequency;
UPS operating with current limitation;
internal fault;
auxiliary control inhibits switching to
Mains 2.
Measurement system
Single-unit or modular UPS
Frequency converter
Static Switch Cubicle
The "Monitor" system displays a
number of input and output
measurements at different points in the
system.
Mains 1
◗◗
phase-to-phase voltages,
◗◗
currents of the three phases,
◗◗
frequency;
Mains 2
◗◗
phase-to-neutral voltage,
◗◗
phase-to-phase voltages,
◗◗
frequency;
battery
◗◗
voltage,
◗◗
charge or discharge current,
◗◗
remaining battery time (calculated for
each UPS);
inverter output
◗◗
phase-to-neutral voltage,
◗◗
phase-to-phase voltages,
◗◗
currents of the three phases,
◗◗
frequency,
◗◗
active and apparent power,
◗◗
ratio peak current / rated current rms;
total load
◗◗
phase-to-neutral voltage,
◗◗
phase-to-phase voltages,
◗◗
currents of the three phases,
◗◗
frequency,
◗◗
active and apparent power;
option
◗◗
battery temperature.
Note:
Frequency converters without batteries
are not concerned by the battery
measurements. The displayed battery
voltage corresponds to the DC voltage
at the RC output.
mains 1
load
mains 2
Q1
Q5N
QF1
Q3BP
Q4S
K3N
inverter
I - P
mains 2
U - F
charger
U  - I - F
battery
U - I
inverter
U - F
load
U - I - F - P
mains 1
common
load
Q1
Q5N
QF1
K3N
inverter
I - P
charger
U  - I - F
battery
U - I
inverter
U - F
load
U - I - F - P
RCIB line(s)
load
mains 2
Q5N
Q3BP
Q4S
mains 2
U - F
load
U - I - F - P
K2S
"Monitor" alphanumeric display
 (cont.)